Special purpose containers

Container field power plant KEP.1000-01

The set of Container Field Power Plant KEP.1000-01 (1000 kW of power) consists of four
container modules:
 
  • Container Power Generator KZP.280-01 (280 kW of power) – 2 pcs.
  • Container Power Generator KZP.440-01 (440 kW of power) – 1 pc.
  • Power Distribution Container KRZ.1000-01 – 1 pc.

Each of those container modules is built on a basis of standard 20’ 1CC ISO container. The power plant can be used both as main or backup source of power, also in a continuous (24h) mode.

The implementation of advanced control solution allows the synchronic mode of work with the power of all modules combined, as well as the sequential work of each power generator. Each container is equipped with the hydraulic reloading and self-leveling system.


Technical parameters

 
Voltage 3 x 400/230 V
Rated power 1250 (2 x 350 + 1 x 550) / 1000 (2 x 280 + 1 x 440) kVA/kW
Power factor 0,8 cos φ
Rated current In = 1810 A
Frequency 50 Hz
Start electric starter
Engine MTU 2 x 8V1600G10F + 1 x 12V1600G10F
Fuel diesel oil
Engine capacity 2 x 14000 + 1 x 21000 cm³
Number of cylinders 2 x 8 + 1 x 12
Rotational speed 1500 rot/min
Rotational speed regulator ECV
Fuel consumption 2 x 63 + 1 x 80 l/h
Cooling factor liquid
Generator type Brushless, synchronic, self-excited 2 x LSA 47.2 S4 + 1 x LSA
47.2 L9
Voltage regulator DVR
Dimensions (lenghth/width/heighth) 4 x 20’ 1CC container (6058/2438/2599 mm)
Fuel tank capacity 2 x 2000 + 1 x 2300 l
Working time with full tank min. 24 h

 
Follow us on Facebook download our brochure